Distribution Equivalent Type Model: Distribution
To be documented.
Model Equations and/or Block Diagrams
This equivalent model and the parameters used for the Load Distribution Equivalent Types are the same as the first 17 parameters of the CMPLDW load characteristic model, along with an MVA base parameter.
Model supported by PowerWorld
Parameters:
| Number | Number: field not used inside Simulator. This is an identifier which is used to maintain compatibility with the negative numbers used within the DYD syntax. When writing out to a DYD file, we will automatically ensure uniqueness across all load components and distribution equivalents. |
| XFMinkV | XFMinkV: when a load has a terminal bus nominal kV below this value, then the transformer of the distribution equivalent will be ignored during the transient stability simulation |
| Mbase | Mbase: Determines how the distribution equivalent MVABase is calculated for loads. |
| Mbase>0 means DistMVABase = Mbase; | Mbase<0 means DistMVABase = LoadMW/abs(Mbase); |
| Mbase=0 means DistMVABase = LoadMW/0.8. | Each load record can override this by specifying the TSDistEquivMVABase directly as well. |
| Bss | Bss: Substation shunt capacitor susceptance, p.u. |
| Rfdr | Rfdr: Feeder equivalent resistance, p.u. |
| Xfdr | Xfdr: Feeder equivalent reactance, p.u. |
| Fb | Fb: Fraction of feeder shunt capacitance at substation bus end |
| Xxf | Xxf: Substation transformer reactance, p.u. |
| Tfixhs | Tfixhs: Transformer high side fixed tap, p.u. |
| Tfixls | Tfixls: Transformer low side fixed tap, p.u. |
| LTC | LTC: 1 for automatic tap adjustment (low side variable tap) |
| Tmin | Tmin: Minimum variable tap, p.u. |
| Tmax | Tmax: Maximum variable tap, p.u. |
| step | step: Variable tap step size, p.u. |
| Vmin | Vmin: Minimum low-side voltage, p.u. |
| Vmax | Vmax: Maximum low-side voltage, p.u. |
| Tdel | Tdel: Time delay to initiate tap adjustment, sec. |
| Tdelstep | Tdelstep: Time delay between tap steps, sec. |
| Rcmp | Rcmp: Transformer LTC compensating resistance, p.u. |
| Xcmp | Xcmp: Transformer LTC compensating reactance, p.u. |